Approximately 7% of iOS devices in our EU data center were temporarily unavailable for customer test sessions after a loss of power to the rack hosting them.
The power circuit feeding the affected rack exceeded its capacity, and a protective breaker tripped to safeguard the line - cutting power to the devices on that rack until the circuit was restored.
The affected circuit was reset and power restored to the rack, returning the devices to customer service.
We are redistributing power load across affected racks, adding capacity monitoring with early-warning alerts ahead of circuit limits, and introducing a capacity review before new devices are deployed to a rack.